Process cooling units SUK/DV
Operating temperatures from -100 up to 150 °C

Technical data Standard Modules


More information about technical Standard > Standard

Series

SUK 150 W/L

SUK 250 W/L

SUK 350 W/L

SUK 400 W/L

SUK 600 W/L

Heat transfer fluid

Water/ Glycol/ Thermal oil/ Special fluids

Water/ Glycol/ Thermal oil/ Special fluids

Water/ Glycol/ Thermal oil/ Special fluids

Water/ Glycol/ Thermal oil/ Special fluids

Water/ Glycol/ Thermal oil/ Special fluids

Operating temperature (°C)

-40...150

-50...150

-70...150

-100...150

-100...150

Pump capacity (m3/h)

0,5...2

2...6

2...20

4...30

5...50

Electric heating (kW)

up to 9

up to 18

up to 50

up to 60

up to 120

One-stage compressor

Cooling capacity (kW) at 20 °C

up to 10

up to 20

up to 50

up to 150

up to 300

Cooling capacity (kW) at 0 °C

up to 5

up to 15

up to 35

up to 120

up to 240

Cooling capacity (kW) at -20 °C

up to 3

up to 6

up to 18

up to 60

up to 120

Cooling capacity (kW) at -40 °C

up to 1

up to 2

up to 7

up to 45

up to 90

Two-stage compressor

Cooling capacity (kW) at -50 °C

up to 1

up to 4

up to 35

up to 70

Two-cascade switching

Cooling capacity (kW) at -60 °C

up to 3

up to 25

up to 50

Cooling capacity( kW) at -70 °C

up to 2

up to 10

up to 20

Cooling capacity (kW) at -80 °C

up to 0,5

up to 5

up to 10

Overall dimensions WxDxH (mm)

400x800x 1000

500x1000x 1500

800x1700x 1500

1000x1500x 1900

1500x2200x 2000

500x1000x 1500

600x1500x 1500

1000x1500x 1900

1300x1900x 2000

2000x2500x 2000

Explosion-proof types available for all units.